TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Date: 4/28/2006 Customer: HVES Circuit/Location: Unit 43 Manufacturer: Howard Industries KVA?TYPE or M/N: 1000 Serial Number: 1865850906 TEST IN SERVICE NORMS* RESULTS Hydrogen (H2) 240 ppm 9 PPM Methane (CH4) 160 ppm 2 PPM Ethane (C2H6) 115 ppm 2 PPM Ethylene (C2H4) 190 ppm 5 PPM Acetylene (C2H2) 11 ppm 0 PPM Carbon Monoxide (CO) 580 ppm 28 PPM Carbon Dioxide (CO2) n/a 257 PPM Nitrogen (N2) n/a 69750 PPM Oxygen (02) n/a 17070 PPM TOTAL GAS n/a 87123 PPM TOTAL COMBUSTIBLES n/a 46 PPM Estimated TCG n/a 0.05 % CO2/CO Ratio: 9.34 ANALYSIS: All gases are within accepted limits. RECOMMENDATION: Resample in 1 year. *In-Service Norms as follows Generating Transmission H2 240 ppm 100 ppm CH4 160 ppm 120 ppm C2H6 115 ppm 65 ppm C2H4 190 ppm 30 ppm C2H2 11 ppm 35 ppm CO 580 ppm 350 ppm
Return to Unit Menu