TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Customer: HVES Date: 04/21/2004
Equipment/Unit Location: HVES 41
Manufacturer: Areva
Serial Number: PJD - 0274
TEST IN SERVICE NORMS* RESULTS
Hydrogen (H2) 240 ppm 4 PPM
Methane (CH4) 160 ppm 0 PPM
Acetylene (C2H2) 11 ppm 0 PPM
Ethylene (C2H4) 190 ppm 1 PPM
Ethane (C2H6) 115 ppm 0 PPM
Carbon Monoxide (CO) 580 ppm 12 PPM
Carbon Dioxide (CO2) n/a 265 PPM
Oxygen (02) n/a 22163 PPM
Nitrogen (N2) n/a 65845 PPM
TOTAL GAS n/a 88290 PPM
TOTAL COMBUSTIBLES n/a 16 PPM
Estimated TCG n/a 0.02 %
ANALYSIS: All gases are within accepted limits.
RECOMMENDATION: Resample in year.
* In-Service Norms as follows-
Generating Transmission
H2 240 ppm 100 ppm
CH4 160 ppm 120 ppm
C2H2 11 ppm 35 ppm
C2H4 190 ppm 30 ppm
C2H6 115 ppm 65 ppm
CO 580 ppm 350 ppm
The above analysis were performed using TOGAS direct injection system
rather than the vacum extraction method described in ASTM D3612.
|