Transformer Data Sheet
Date Tested: 04/20/2004 Customer Name: HVES Circuit Name: HVES 41 Transformer Type: Pad mount Number: PJD - 0274 Class: OA Three Phase 60 Hertz Manufacturer: Areva Voltage Rating: 13200Y/7620 - 480Y/277 LV winding: AL KVA Ratings: 2500 Continuous, Self Cooled HV winding: AL Continuous, Forced Air LV: 65 C rise, BIL: 30 KV HV: 65 C rise, BIL: 95 KV Approx. Weight in Pounds - Core & Coils : 5271 Case & Fittings : Total : 12460 Impedance Volts: 5.55 percent at rated volts at: 2500 KVA.
Transformer Test Data
	  Megger Test Results --
High  ->  Ground :  29.4k  M Ohms, @: 5KV DC
Low   ->  Ground :  26.2k  M Ohms, @: 1KV DC
High  ->  Low    :  67.0k  M Ohms, @: 1KV DC

Tap (V)    Calc.TTR    Phase1      Phase2     Phase3
14400     : 30.000     : 29.998     : 29.996    : 29.998
13800     : 28.750     : 28.725     : 28.724    : 28.725
13200     : 27.509     : 27.544     : 27.542    : 27.543
12470     : 25.979     : 25.998     : 25.997    : 25.998
12000     : 25.000     : 24.998     : 24.997    : 24.998

Attachment:
Polarization Index / Capacitance test results
     H-G: 1.45 PI  0.02 microfarad Cap.
     H-G: 2.42 PI  0.02 microfarad Cap.
     H-G: 2.88 PI  0.02 microfarad Cap.
Return to Unit Menu
Return to Main Page

All units are ready for immediate rental from our Albany location. Call our office for more details 518-869-4961 or contact us via E-mail at rentals@hvesrents.com.