TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Customer: HVES Date: 01/08/2004
Equipment/Unit Location: HVES 40
Manufacturer: General Electric
Serial Number: Q56900-TIS
TEST IN SERVICE NORMS* RESULTS
Hydrogen (H2) 200 ppm 4 PPM
Methane (CH4) 100 ppm 14 PPM
Acetylene (C2H2) 1 ppm 0 PPM
Ethylene (C2H4) 30 ppm 0 PPM
Ethane (C2H6) 30 ppm 0 PPM
Carbon Monoxide (CO) 3000 ppm 27 PPM
Carbon Dioxide (CO2) n/a 431 PPM
Oxygen (02) n/a 37329 PPM
Nitrogen (N2) n/a 109555 PPM
TOTAL GAS n/a 147360 PPM
TOTAL COMBUSTIBLES n/a 45 PPM
Estimated TCG n/a 0.00 %
ANALYSIS: All gases are within accepted limits.
RECOMMENDATION: Resample in year.
|