Transformer Data Sheet
Date Tested: 01/08/2004 Customer Name: HVES Circuit Name: HVES 40 Transformer Type: Padmount Silicone Number: Q56900-T1S Class: OA Three Phase 60 Hertz Manufacturer: General Electric Voltage Rating: 4800 - 480Y/277 LV winding: AL KVA Ratings: 300 Continuous, Self Cooled HV winding: AL Continuous, Forced Air LV: 65 C rise, BIL: 30 KV HV: 65 C rise, BIL: 60 KV Approx. Weight in Pounds - Core & Coils : 1100 Fluid: 225 gallons 1800 Case & Fittings : 1300 Total : 4200 Impedance Volts: 3.92 percent at rated volts at: 300 KVA.
Transformer Test Data
	  Megger Test Results --
High  ->  Ground :  13.3k  M Ohms, @: 5KV DC
Low   ->  Ground : >1.01k  M Ohms, @: 1KV DC
High  ->  Low    :  28.2k  M Ohms, @: 1KV DC

Tap (V)    Calc.TTR    Phase1      Phase2     Phase3
5040     : 18.195     : 18.169     : 18.172    : 18.170
4920     : 17.762     : 17.778     : 17.781    : 17.778
4800     : 17.329     : 17.343     : 17.346    : 17.344
4680     : 16.895     : 16.908     : 16.911    : 16.910
4560     : 16.462     : 16.474     : 16.477    : 16.475

10 Minute
Megger  Tests:                     Pi      Cap.
          H-G: 24.8k M-Ohms     : 1.86      : .01 microfarad
          L-G:>1.01k M-Ohms     : -         : . -
          H-L: 181k M-Ohms      : 6.45      : .01 microfarad
Return to Unit Menu
Return to Main Page

All units are ready for immediate rental from our Albany location. Call our office for more details 518-869-4961 or contact us via E-mail at rentals@hvesrents.com.