Transformer Data Sheet
Date Tested: 01/08/2004
Customer Name: HVES
Circuit Name: HVES 40
Transformer Type: Padmount Silicone
Number: Q56900-T1S Class: OA Three Phase 60 Hertz
Manufacturer: General Electric
Voltage Rating: 4800 - 480Y/277 LV winding: AL
KVA Ratings: 300 Continuous, Self Cooled HV winding: AL
Continuous, Forced Air LV: 65 C rise, BIL: 30 KV
HV: 65 C rise, BIL: 60 KV
Approx. Weight in Pounds -
Core & Coils : 1100 Fluid: 225 gallons 1800
Case & Fittings : 1300
Total : 4200
Impedance Volts: 3.92 percent at rated volts at: 300 KVA.
Transformer Test Data
Megger Test Results --
High -> Ground : 13.3k M Ohms, @: 5KV DC
Low -> Ground : >1.01k M Ohms, @: 1KV DC
High -> Low : 28.2k M Ohms, @: 1KV DC
Tap (V) Calc.TTR Phase1 Phase2 Phase3
5040 : 18.195 : 18.169 : 18.172 : 18.170
4920 : 17.762 : 17.778 : 17.781 : 17.778
4800 : 17.329 : 17.343 : 17.346 : 17.344
4680 : 16.895 : 16.908 : 16.911 : 16.910
4560 : 16.462 : 16.474 : 16.477 : 16.475
10 Minute
Megger Tests: Pi Cap.
H-G: 24.8k M-Ohms : 1.86 : .01 microfarad
L-G:>1.01k M-Ohms : - : . -
H-L: 181k M-Ohms : 6.45 : .01 microfarad
|