Transformer Data Sheet
Date Tested: 10/21/02 Customer Name: HVES Circuit Name: HVES 37 Transformer Type: Dry Number:QL Class: AA Three Phase 60 Hertz Manufacturer: GE Voltage Rating: 480 Delta - 240 Delta LV winding: AL KVA Ratings: 45 Continuous, Self Cooled HV winding: AL Continuous, Forced Air LV: 150C rise, BIL: 10 KV HV: 150C rise, BIL: 10 KV Approx. Weight in Pounds Core & Coils : Case & Fittings: Total : 360 Impedance Volts: 4.0 percent at rated volts at: 45 KVA.
Transformer Test Data
	  Megger Test Results --
High  ->   Ground : 10k   M Ohms, @: .5KV DC
Low   ->   Ground : 20k   M Ohms, @: .5KV DC
High  ->   Low    : 10k   M Ohms, @: .5KV DC

Tap (V)   Calc.TTR    Phase1    Phase2     Phase3
: 503   : 2.095    : 2.094    : 2.094     : 2.094
: 491   : 2.045    : 2.044    : 2.044     : 2.044
: 480   : 2.000    : 2.000    : 2.000     : 2.000
: 469   : 1.954    : 1.952    : 1.952     : 1.952
: 458   : 1.908    : 1.907    : 1.907     : 1.907
: 443   : 1.845    : 1.845    : 1.845     : 1.845
: 431   : 1.795    : 1.796    : 1.796     : 1.796