TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Customer: HVES Date: 04/25/2000
Equipment/Unit Location: HVES 29
Manufacturer: General Electric
Serial Number: M161189
TEST IN SERVICE NORMS* RESULTS
Hydrogen (H2) 240 ppm <1 PPM
Methane (CH4) 160 ppm 19 PPM
Acetylene (C2H2) 11 ppm <1 PPM
Ethylene (C2H4) 190 ppm <1 PPM
Ethane (C2H6) 115 ppm 5 PPM
Carbon Monoxide (CO) 580 ppm 603 PPM
Carbon Dioxide (CO2) n/a 7724 PPM
Oxygen (02) n/a 2971 PPM
Nitrogen (N2) n/a 77461 PPM
TOTAL GAS n/a 88682 PPM
TOTAL COMBUSTIBLES n/a 627 PPM
Estimated TCG n/a 0.555 %
ANALYSIS: Carbon monoxide level is above the accepted limit. Gas ratios
indicate no fault is present.
RECOMMENDATION: Resample in 6 months.
*In-Service Norms as follows
Generating Transmission
H2 240 ppm 100 ppm
CH4 160 ppm 120 ppm
C2H2 11 ppm 35 ppm
C2H4 190 ppm 30 ppm
C2H6 115 ppm 65 ppm
CO 580 ppm 350 ppm
The above analyses were performed using the TOGAS direct injection system
rather than the vacuum extraction method described in ASTM D3612.
PRO/gasoil
|