Transformer Data Sheet
Date Tested: 04/25/2000 Customer Name: HVES Circuit Name: HVES 29 Transformer Type: Substation Number: M161189 Class: OA Three Phase 60 Hertz Manufacturer: General Electric Voltage Rating: 13200 X 4160/2400 LV winding: CU KVA Ratings: 4000 Continuous, Self Cooled HV winding: CU 5000 Continuous, Forced Air LV: 65 C rise, BIL: 30 KV HV: 65 C rise, BIL: 90 KV Approx. Weight in Pounds - Core & Coils : Case & Fittings: Total : 31600 Impedance Volts: 6.01 percent at rated volts at: 5000 KVA.
Transformer Test Data
	  Megger Test Results --
High  ->   Ground : 3.76k    M Ohms, @: 5KV DC
Low   ->   Ground : 4.82k    M Ohms, @: 5KV DC
High  ->   Low    : 6.50k    M Ohms, @: 5KV DC

Tap (V)   Calc.TTR    Phase1    Phase2    Phase3
:13860     :5.775     :5.776    :5.776    :5.775       
:13530     :5.637     :5.638    :5.639    :5.638       
:13200     :5.500     :5.499    :5.499    :5.499       
:12870     :5.362     :5.361    :5.361    :5.362       
:12540     :5.225     :5.225    :5.225    :5.225       
:           :          :          :       

Attachment:  Unit has HV roof bushings and LV sidewall bushings.
Polarization Index     Capacitance
H-G: 1.82             .03 microfarad
L-G: 2.32             .02 microfarad
H-L: 2.60             .02 microfarad
			