TRANSFORMER OIL TESTSStandard Oil Analysis
Customer: HVES Date: 3/16/02006 Equipment/Unit: Location: Unit 20 Manufacturer: Howard KVA/TYPE or M/N: 2500 Serial Number: 5777765005 TEST ASTM NO. LIMITS* RESULTS Dielectric D-877 26 min. : 46 kV Neutrality D-974 0.10 max. : 0.002 Specific Gravity D-1298 0.91 max. : 0.890 Color D-1500 3.5 max. : <0.5 mg KOH/g IFT D-971 32 min. : 48.5 Dynes/ppm Visual D-1524 n/a : Clear & bright Water D-1533 20 max. : 4 PPM * IEEE Limits - Acceptable limits for the IEEE classification of oils for continued service, EPRI Utility Survey 1977. COMMENTS: PRO/stdoil