TRANSFORMER OIL TESTSStandard Oil Analysis
Customer: HVES Date: 05/01/03
Equipment/Unit Location: HVES 19
Manufacturer: Alstom
Serial Number: PID-0297
TEST ASTM NO. LIMITS* RESULTS
Dielectric D-877 27 min. : 44 kV
Neutrality D-974 0.30 max. : 0.001 mg KOH/g
Specific Gravity D-1298 n/a : 0.888
Color D-1524 n/a : <0.5
IFT D-971 24 min. : 47.9 Dynes/ppm
Visual D-1524 n/a : Clear & Bright
Water D-1533 34 max. : 5 ppm
* IEEE Limits - Acceptable limits for the IEEE classification of oils for
Continued service, EPRI Utility Survey 1977.
COMMENTS:
PRO/stdoil
|