Transformer Data Sheet
Date Tested: 09/23/99
Customer Name: HVES
Circuit Name: HVES 18
Transformer Type: Padmount
Number: PEI-1075 Class: OA Three Phase 60 Hertz
Manufacturer: ALSTOM
Voltage Rating: 480 DELTA 208Y/120 LV winding: AL
KVA Ratings: 1000 Continuous, Self Cooled HV winding: AL
Continuous, Forced Air LV: 65 C rise, BIL: 30 KV
HV: 65 C rise, BIL: 45 KV
Approx. Weight in Pounds -
Core & Coils : 2651 OIL: 1904
Case & Fittings:
Total : 7030
Impedance Volts: 7.10 percent at rated volts at: 1000 KVA.
Transformer Test Data
Megger Test Results --
High -> Ground : 1.31 M Ohms, @: 1KV DC
Low -> Ground : 326 M Ohms, @:.5KV DC
High -> Low : 3.42 M Ohms, @:.5KV DC
Tap (V) Calc.TTR Phase1 Phase2 Phase3
480 4.0 3.997 3.998 3.995
POLARIZATION INDEX: H-G: 1.54 CAPACITENCE IN RICO-FARAD H-G: 0.01
L-G. 3.14 L-G: 0.01
H-L: 1.94 H-L: 0.02
|