Transformer Data Sheet
Date Tested: 09/23/99 Customer Name: HVES Circuit Name: HVES 15 Transtormer Type: Padmount Number: PEI-1090 Class: OA Three Phase 60 Hertz Manufacturer: ALSTOM Voltage Rating: 2400Y/1386 480Y/277 LV winding: AL KVA Ratings: 2000 Continuous, Self Cooled HV winding: AL Continuous, Forced Air LV: 65 C rise, BIL: 30 KV HV: 65 C rise, BIL: 43 KV Approx. Weight in Pounds - Core & Coils : 4350 OIL: 3301 Case & Fittings: Total : 11610 Impedance Volts: 5.74 percent at rated volts at: 2000 KVA.
Transformer Test Data
	  Megger Test Results ---
High  ->  Ground : 3.32 M Ohms, @: 5KV DC
Low   ->  Ground : 3.38 M Ohms, @: 1KV DC
High  ->  Low    : 2.42 M Ohms, @: 1KV DC

Tap (V)  Calc.TTR   Phase1     Phase2     Phase3
2520     :5.250     :5.231    : 5.230    : 5.231
2460     :5.125     :5.155    : 5.153    : 5.154
2400     :5.000     :4.999    : 5.000    : 5.000
2340     :4.875     :4.846    : 4.846    : 4.846
2280     :4.750     :4.769    : 4.770    : 4.756

POLARIZATION INDEX: H-G: 1.43     CAPACITENCE IN PICO-FARAD H-G: 0.02
                    L-G: 1.48                               L-G: 0.02
                    H-L: 0.98                               H-L: 0.02
Return to Unit Menu
Return to Main Page

All units are ready for immediate rental from our Albany location. Call our office for more details 518-869-4961 or contact us via E-mail at rentals@hvesrents.com.