TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Customer: HVES Date: 09/23/99
Equipment/Unit Location: HVES 14
Manufacturer: Alstom
Serial Number: PEI-1077
TEST IN SERVICE NORMS* RESULTS
Hydrogen (H2) 240 ppm <1 PPM
Methane (CH4) 160 ppm <1 PPM
Acetylene (C2H2) 11 ppm <1 PPM
Ethylene (C2H4) 190 ppm 1 PPM
Ethane (C2H6) 115 ppm <1 PPM
Carbon Monoxide (CO) 580 ppm 15 PPM
Carbon Dioxide (CO2) n/a 302 PPM
Oxygen (02) n/a 17674 PPM
Nitrogen (N2) n/a 54239 PPM
TOTAL GAS n/a 72231 PPM
TOTAL COMBUSTIBLES n/a 16 PPM
Estimated TCG n/a 0.017 %
ANALYSIS: All gases are within the accepted limits.
RECOMMENDATION: Resample in 1 year.
*In-Service Norms as follows
Generating Transmission
H2 240 ppm 100 ppm
CH4 160 ppm 120 ppm
C2H2 11 ppm 35 ppm
C2H4 190 ppm 30 ppm
C2H6 115 ppm 65 ppm
CO 580 ppm 330 ppm
The above analyses were performed using the TOGAS direct injection system
rather than the vacuum extraction method described in ASTM D3612.
PRO/gasoil
|