Transformer Data Sheet
Data Tested: 09/23/99 Customer Name: HVES Circuit Name: HVES 14 Transformer Type: Padmount Number: PEI-1077 Class: OA Three Phase 60 Hertz Manufacturer: ALSTOM Voltage Rating: 4160 X 2400 DELTA 208Y/120 LV winding: AL KVA Ratings: 500 Continuous, Self Cooled HV winding: AL Continuous, Forced Air LV: 65 C rise, BIL: 30 KV HV: 65 C rise, BIL: 60 KV Approx. Weight in Pounds - Core & Coils : 1822 OIL: 1271 Case & Fittings: Total : 4510 Impedance Volts: 5.19 percent at rated volts at: 500 KVA.
Transformer Test Data
	  Megger Test Results --
High  ->  Ground : 370   M Ohms, @: 5KV DC
Low   ->  Ground : 185   M Ohms, @:.5KV DC
High  ->  Low    : 356 5 M Ohms, @:.5KV DC

Tap (V)   Calc.TTR   Phase1    Phase2     Phase3
4368    : 36.40    : 36.493   : 36.374   : 36.373
4264    : 35.53    : 35.494   : 35.497   : 35.492
4160    : 34.66    : 34.620   : 34.623   : 34.618
4056    : 33.80    : 33.744   : 33.743   : 33.743
3952    : 32.93    : 32.870   : 32.874   : 32.874
2400    : 20       : 19.997   : 19.999   : 19.996

POLARIZATION INDEX: H-G: 1.29     CAPACITENCE IN PICO-FARAD H-G: 0.01
                    L-G: 1.14                               L-G: 0.01
                    H-L: 1.07                               H-L: 0.01