TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Customer: HVES Date: 02/19/99
Equipment/Unit Location: HVES 12
Manufacturer: General Electric
Serial Number: ST079555327
TEST IN SERVICE NORMS* RESULTS
Hydrogen (H2) 240 ppm <1 PPM
Methane (CH4) 160 ppm 14 PPM
Acetylene (C2H2) 11 ppm <1 PPM
Ethylene (C2H4) 190 ppm 10 PPM
Ethane (C2H6) 115 ppm 7 PPM
Carbon Monoxide (CO) 580 ppm 315 PPM
Carbon Dioxide (CO2) n/a 4917 PPM
Oxygen (02) n/a 9641 PPM
Nitrogen (N2) n/a 62545 PPM
TOTAL GAS n/a 77450 PPM
TOTAL COMBUSTIBLES n/a 346 PPM
Estimated TCG n/a 0.343 %
ANALYSIS: All gases are within the accepted limits.
RECOMMENDATION: Resample in 1 year.
*In-Service Norms as follows
Generating Transmission
H2 240 ppm 100 ppm
CH4 160 ppm 120 ppm
C2H2 11 ppm 35 ppm
C2H4 190 ppm 30 ppm
C2H6 115 ppm 65 ppm
CO 580 ppm 350 ppm
The above analyses were performed using the TOGAS direct injection system
rather than the vacuum extraction method described in ASTM D3612.
PRO/gasoil
|