TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Customer: HVES Date: 02/19/99 Equipment/Unit Location: HVES 12 Manufacturer: General Electric Serial Number: ST079555327 TEST IN SERVICE NORMS* RESULTS Hydrogen (H2) 240 ppm <1 PPM Methane (CH4) 160 ppm 14 PPM Acetylene (C2H2) 11 ppm <1 PPM Ethylene (C2H4) 190 ppm 10 PPM Ethane (C2H6) 115 ppm 7 PPM Carbon Monoxide (CO) 580 ppm 315 PPM Carbon Dioxide (CO2) n/a 4917 PPM Oxygen (02) n/a 9641 PPM Nitrogen (N2) n/a 62545 PPM TOTAL GAS n/a 77450 PPM TOTAL COMBUSTIBLES n/a 346 PPM Estimated TCG n/a 0.343 % ANALYSIS: All gases are within the accepted limits. RECOMMENDATION: Resample in 1 year. *In-Service Norms as follows Generating Transmission H2 240 ppm 100 ppm CH4 160 ppm 120 ppm C2H2 11 ppm 35 ppm C2H4 190 ppm 30 ppm C2H6 115 ppm 65 ppm CO 580 ppm 350 ppm The above analyses were performed using the TOGAS direct injection system rather than the vacuum extraction method described in ASTM D3612. PRO/gasoil
Return to Unit Menu
Return to Main Page

All units are ready for immediate rental from our Albany location. Call our office for more details 518-869-4961 or contact us via E-mail at rentals@hvesrents.com.