Transformer Data Sheet
Date Tested: 06/15/99 Customer Name: HVES Circuit Name: HVES #11 Transformer Type: Pad Mount Number: PEE-0654 Class: OA Three Phase 60 Hertz Manufacturer: Alstom Voltage Rating: 416OX2400 Delta 48OY277 LV winding: AL KVA Ratings: 1000 Continuous, Self Cooled HV winding: AL Continuous, Forced Air LV: 65 C rise, BIL: 30 KV HV: 65 C rise, BIL: 60 KV Approx. Weight in Pounds - Core & Coils : 2653 Oil: 1986 Case & Fittings: 2441 Total : 7080 Impedance Volts: 5.77 percent at rated volts at: 1000 KVA.
Transformer Test Data
	  Megger Test Results
High  ->   Ground   : 67.5 M Ohms, @: 5KV DC
Low   ->   Ground   : 93.0 M Ohms, @: 1KV DC
High  ->   Low      : 37.6 M Ohms, @: 1KV DC

Tap (V)   Calc.TTR     Phase1    Phase2       Phase3
4368   :  15.768     : 15.763    : 15.765    : 15.763               PI Data:
4264   :  15.394     : 15.411    : 15.412    : 15.410                    H-G:   2.12
4160   :  15.018     : 14.998    : 15.000    : 14.998                    L-G:   1.61
4056   :  14.643     : 14.646    : 14.647    : 14.646                    H-L:   3.28
3952   :  14.267     : 14.234    : 14.236    : 14.234
                                                                    Capacitance:
                                                                         H-L:   .01
Tap (C)   Calc.TTR     Phase1    Phase 2      Phase 3                    L-G:   .01
8.664  :  8.647      : 8.647     : 8.647     : 8.647                     H-L:   .02
Return to Unit Menu
Return to Main Page

All units are ready for immediate rental from our Albany location. Call our office for more details 518-869-4961 or contact us via E-mail at rentals@hvesrents.com.