TRANSFORMER OIL TESTSDissolved Gas-in-oil Analysis
Customer: HVES Date: 03/15/1999
Equipment/Unit Location: HVES 10
Manufacturer: HK Porter Co. Inc.
Serial Number: W242616
TEST IN SERVICE NORMS* RESULTS
Hydrogen (H2) 240 ppm <20 PPM
Methane (CH4) 160 ppm 7 PPM
Acetylene (C2H2) 11 ppm <2 PPM
Ethylene (C2H4) 190 ppm 72 PPM
Ethane (C2H6) 115 ppm 2 PPM
Carbon Monoxide (CO) 580 ppm 102 PPM
Carbon Dioxide (CO2) n/a 2711 PPM
Oxygen (02) n/a 28553 PPM
Nitrogen (N2) n/a 62354 PPM
TOTAL GAS n/a 93805 PPM
TOTAL COMBUSTIBLES n/a 187 PPM
Estimated TCG n/a 0.105 %
ANALYSIS: Ethylene level is above the accepted limit. Gas ratios indicate
overheating of the oil.
RECOMMENDATION: Resample in 6 months.
*In-Service Norms as follows -
Generating Transmission
H2 240 ppm 100 ppm
CH4 160 ppm 120 ppm
C2H2 11 ppm 35 ppm
C2H4 190 ppm 30 ppm
C2H6 115 ppm 65 ppm
Co 580 ppm 350 ppm
The above analyses were performed using the TOGAS direct injection system
rather than the vacuum extraction method described in ASTM D3612.
PRO/gasoil
|