Transformer Data Sheet
Date Tested: 03/12/99
Customer Name: HVES
Circuit Name: HVES 10
Transformer Type: PT
Number: W242616 Class: OA Three Phase 60 Hertz
Manufacturer: HK Porter Co Inc.
Voltage Rating: 34400 2400/4160y/2400 LV winding:
KVA Ratings: 5000 Continuous, Self Cooled HV winding:
Continuous, Forced Air LV: 55 C rise, BIL: 75 KV
HV: 55 C rise, BIL: 200KV
Approx. Weight in Pounds -
Core & Coils : 13900
Case & Fittings : 10430 (1430 gals. oil #10670)
Total : 35000
Impedance Volts: 11.2 percent at rated volts at: 5000 KVA.
Transformer Test Data
Megger Test Results --
High -> Ground : M Ohms, @: 5KV DC
Low -> Ground : M Ohms, @: 5KV DC
High -> Low : M Ohms, @: 5KV DC
Tap (V) Calc.TTR Phase1 Phase2 Phase3
:36200 : 15.083 :15.052 :15.070 : 15.065
:35300 : 14.708 :14.690 :14.702 : 14.696
:34400 : 14.333 :14.309 :14.319 : 14.314
:33SOO : 13.958 :13.927 :13.938 : 13.932
:32600 : 13.583 :13.558 :13.569 : 13.565
1 Min 10 Min PI Data
Megger Test: H-G: 90.5M 160M 1.77
L-G 565M 680M 1.20
H-L 515M 490M .95
Attachment:
Can be delta on secondary DW & P No 719 1970.
HV: Amps: Position: Taps:
32600 79.8 1 4+5
35300 81.8 2 3+5
34400 84.0 3 3+6
33500 86.2 4 2+6
32600 88.6 5
High Voltage Bushings
CAT: 7B536G6 HI- 1679859 Capacitance .355
Type: u H2- 1679858 Capacitance .354
Class: AT 34.5 H3- 1679860 Capacitance .360
Amps: 400
BIL: 200
Year: 1969
|