TRANSFORMER OIL TESTSStandard Oil Analysis
Customer: HVES Date: 12/28/98 Equipment/Unit Location: HVES 8 Manufacturer: T69857375-37-R Serial Number: Sunbelt TEST ASTM NO. LIMITS* RESULTS Dielectric D-877 27 min. 44 kV Neutrality D-974 0.30 max. .009 mg KOH/g Specific Gravity D-1298 n/a .891 Color D-1524 n/a 0.5 IFT D-971 24 min. 34.7 Dynes/ppm Visual D-1524 n/a Clear Water D-1533 34 max. 1 PPM * IEEE Limits - Acceptable limits for the IEEE classification of oils for continued service, EPRI Utility Survey 1977. COMMENTS: PRO/stdoil
Return to Unit Menu
Return to Main Page

All units are ready for immediate rental from our Albany location. Call our office for more details 518-869-4961 or contact us via E-mail at rentals@hvesrents.com.