Transformer Data Sheet
Date Tested: 06/Ol/1998 Customer Name: HVES Circuit Name: HVES 8 Tranformer Type: Substation Number:ST6985737537R Class: OA/FA Three Phase 60 Hertz Manufacturer: RTE Voltage Rating: 13,800-4,160Y/2400 LV winding: CU KVA Ratings: 3750 Continuous, Self Cooled HV winding: CU 5249 Continuous, Forced Air LV: 55 C rise, BIL: 60 KV HV: 65 C rise, BIL: 95 KV Approx. Weight in Pounds - Core & Coils Case & Fittings: Total : 24,000 Impedance Volts: 6.23 percent at rated volts at: 3750 KVA.
Transformer Test Data
	  Megger Test Results --
High  ->  Ground : 25k    M Ohms,      5KV DC
Low   ->  Ground : 20k    M Ohms,      5KV DC
High  ->  Low    : 45k    M Ohms,      5KV DC

Tap (Y)  Calc.TTR   Phase1    Phase2    Phase3
13800   : 5.750    :5.757     :5.758    : 5.757
13455   : 5.606    :5.627     :5.627    : 5.628
13110   : 5.500    :5.483     :5.483    : 5.483
12765   : 5.319    :5.337     :5.338    : 5.338
12420   : 5.175    :5.192     :5.193    : 5.193