Transformer Data Sheet
Date Tested: 05/22/2000 Customer Name: HVES Circuit Name: HVES 7 Transformer Type: Substation Number: TSP-0698 Class: OA/FAAThree Phase 60 Hertz Manufacturer: SD Myers Voltage Rating: 13,800-4,160Y/2400 LV winding: CU KVA Ratings: 3750 Continuous, Self Cooled HV winding: CU Continuous, Forced Air LV: 65 C rise, BIL: 60 KV HV: 65 C rise, BIL: 95 KV Approx. Weight in Pounds Core & Coils Case & Fittings: Total : 15,000 Impedance Volts: 6.28 percent at rated volts at: 3750 KVA.
Transformer Test Data
	  Megger Test Results --
High  ->   Ground  : 10k   M Ohms,       5KV DC
Low   ->   Ground  : 20k   M Ohms,       5KV DC
High  ->   Low     : 10k   M Ohms,       5KV DC

Tap (V)  Calc.TTR    Phase1    Phase2     Phase3
14400   : 6.000     :5.990     :5.990     :5.990
14100   : 5.875     :5.872     :5.872     :5.872
13800   : 5.75O     :5.757     :5.757     :5.757
135OO   : 5.625     :5.628     :5.628     :5.628
13200*  : 5.5OO     :5.500     :5.500     :5.500


Attachment: Left on #5/13200V tap as required.