TRANSFORMER OIL TESTSStandard Oil Analysis
Customer: HVES Date: 10/28/98 Equipment/Unit Location: HVES 6 Manufacturer: Alstom Serial Number: PDJ-1212 TEST ASTM NO. LIMITS* RESULTS Dielectric D-877 27 min. 49 kV Neutrality D-974 0.30 max. .006 mg KOH/g Specific Gravity D-1298 n/a .888 Color D-1524 n/a 0.5 IFT D-971 24 min. 37.4 Dynes/ppm Visual D-1524 n/a Clear Water D-1533 34 max. 5 PPM * IEEE Limits - Acceptable limits for the IEEE classification of oils for continued service, EPRI Utility Survey 1977. COMMENTS: PRO/stdoil