Transformer Data Sheet
Date Tested: 10/23/98
Customer Name: HVES
Circuit Name: HVES 6
Transformer Type: Pad/oil
Number: PDJ-1212 Class: OA Three Phase 60 Hertz
Manufacturer: Alstom
Voltage Rating: 480 Delta/208Y-120 LV winding: AL
KVA Ratings: 1000 Continuous, Self Cooled HV winding: AL
: 1120 Continuous, Forced Air LV: 55 C rise, BIL: 30 KV
HV: 65 C rise, BIL: 30 KV
Approx. Weight in Pounds -
Core & Coils :
Case & Fittings:
Total : 8350
Impedance Volts: 7.34 percent at rated volts at: 1000 KVA.
Transformer Test Data
Megger Test Results --
High -> Ground : 44.6K M Ohms, @: 1KV DC
Low -> Ground : 52.0K M Ohms, @:.5KV DC
High -> Low : 170K M Ohms, @:.5KV DC
Tap (V) Calc.TTR Phase1 Phase2 Phase3
480 : 4.000 : 3.999 : 4.000 : 3.999
Attachment: PI H-G 1.14 Capacitance .01 microfarad
L-G 1.50 .02
H-L 1.99 .03
|