TRANSFORMER OIL TESTSStandard Oil Analysis
Customer: HVES Date: 05/01/03 Equipment/Unit Location: HVES 4 Manufacturer: ALSTOM Serial Number: PID-0296 TEST ASTM NO. LIMITS* RESULTS Dielectric D-877 27 min. : 47 kV Neutrality D-974 0.30 max. : 0.001 mg KOH/g Specific Gravity D-1298 n/a : 0.890 Color D-1524 n/a : < 0.5 IFT D-971 24 min. : 47.0 Dynes/ppm Visual D-1524 n/a : Clear & Bright Water D-1533 34 max. : 5 PPM * IEEE Limits - Acceptable limits for the IEEE classification of oils for continued service, EPRI Utility Survey 1977. COMMENTS: PRO/stdoil