Transformer Data Sheet
Date Tested: 03/03/98 Customer Name: HVES Circuit Name: HVES 3 Transformer Type: OIL Number: PDB-0205 Class: OA Three Phase 60 Hertz Manufacturer: GE ALSTHOM Voltage Rating: 13,200 - 480Y/277 LV winding: AL KVA Ratings: 2,000 Continuous, Self Cooled HV winding: AL Continuous, Forced Air LV: 65 C rise, BIL: 30 KV HV: C rise, BIL: 95 KV Approx. Weight in Pounds -- Core & Coils : Case & Fittings : Total : 11,550 Impedance Volts: 6.13 percent at rated volts at: 2,000 KVA.
Transformer Test Data
Megger Test Results -- High -> Ground : 44.2 KM Ohms, @: 5KV DC Low -> Ground : 6.65 KM Ohms, @: 1KV DC High -> Low : 43.4 KM Ohms, @: 1KV DC Tap (V) Calc.TTR Phase1 Phase2 Phase3 :14400 : 51.986 :52.004 : 52.008 :52.080 :13800 : 49.819 :49.837 : 49.842 :49.914 :13200 : 47.653 :47.668 : 47.675 :47.747 :12470 : 45.018 :45.001 : 45.007 :45.079 :12000 : 43.321 :43.337 : 43.338 :43.413 Attachment: 1 MIN. PI CAPACITENCE 20.8 KM 2.12 0.01 MICROFARAD 4.54 KM 1.46 0.01 MICROFARAD 37.0 KM 1.17 0.01 MICROFARAD