Customer Name: HVES Date Tested:
US: #1 FDR: Manufacturer:
Type: Serial Number:
KV Rating: WLI Amps: 600 Duty Cycle:
Interrupting Capacity: 14KA Publications:
Environment -
: Indoor : X Outdoor
: X Wet : Dry : X Clean : Dirty
HIGH VOLTAGE SWITCH TEST DATA
I . Inspect insulators
for breaks, cracks, or burns. - OK: X Not OK: Corrected:
2. Inspect contacts for alignment,
pressure, burns, or corrosion. - OK: X Not OK: Corrected:
3. Check for proper lubrication,
wipes, gaps, and clearances.
Check blade lock or latch. - OK: X Not OK: Corrected:
4. Inspect interphase mechanical.
linkages, operating rods,
levers, bearings for adjustment,
lubrication, tightness, or
damage. - OK: X Not OK: Corrected:
5. Check that Ground Straps and
ground slip rings have good
contact. - OK: X Not OK: Corrected:
6. Inspect overall switch including
controls and indicators for
good working condition. - OK: X Not OK: Corrected:
7. Measure the closed contact resistance with low resistance ohmmeter.
Phase 1: 39 Micro-ohms. OK: X Not OK: Correction Required:
Phase 2: 32 Micro-ohms. OK: X Not OK: Correction Required:
Phase 3: 34 Micro-ohms. OK: X Not OK: Correction Required:
8. Megger Readings -
Primary
A: 100K M Ohms B: 100K M Ohms C: 100K M Ohms
A-B: 100K M Ohms A-C: 100K M Ohms B-C: 100K M Ohms
Secondary
A: 100K M Ohms B: 100K M Ohms C: 100K M Ohms
A-B: 100K M Ohms A-C: 100K M Ohms B-C: 100K M Ohms
Other General Comments:
|